E&H PMP50 pressure transmitter

Model:PMP50-AABAAJA6AA3HAA1SA0A1

Manufacturer: ENDRESS + HAUSER

Size: 25*25*35cm

Detail Specification: pressure transmitter

Comment:Carton

Shipping Weight: 8Kg

Estimated Lead Time: 12 Weeks

Payment:T/T

HS CODE:9026201090

product details

E&H PMP50 pressure transmitter

Product Overview

The Endress+Hauser Cerabar PMP50 is a high-performance pressure transmitter featuring a metal membrane sensor, specifically engineered for precise measurement of liquids and gases. Optimized for standard industrial applications, the PMP50 series delivers intuitive and safe operating functions while maintaining exceptional measurement integrity across diverse process conditions

As part of Endress+Hauser‘s Cerabar product family, the PMP50 operates on the principle of absolute and gauge pressure measurement, offering a practical solution for engineers and plant operators requiring reliable pressure monitoring without unnecessary complexity.

Key Technical Specifications

Pressure Measurement Range

The Cerabar PMP50 supports a broad pressure measurement spectrum, accommodating measuring cells from 1 bar up to 400 bar (14.5 psi to 5800 psi). The maximum pressure rating extends to 400 bar (6000 psi), while the overpressure limit reaches an impressive 600 bar (9,000 psi) for standard configurations and up to 2,800 bar (40,610 psi) under specific conditions.

Smallest calibratable span: 20 mbar (0.29 psi)

Maximum turndown ratio: 20:1

Vacuum resistance: 50 mbar (0.73 psi)

Accuracy Performance

The PMP50 series offers two distinct accuracy classes to match varying application requirements:

Performance Class Reference Accuracy
Standard up to ±0.065%
Platinum up to ±0.055%

Long-Term Stability

Measurement consistency over extended operational periods is a hallmark of the PMP50 design. Long-term stability specifications include:

0.05% to 0.1% of URL per year

0.13% to 0.2% of URL over 5 years

0.23% to 0.25% of URL over 10 years

The Platinum version delivers the more conservative drift figures, ensuring sustained accuracy for critical applications.

Temperature Ranges

The Cerabar PMP50 accommodates a wide array of thermal environments:

Configuration Process Temperature Range
Standard (without diaphragm seal) -40°C to +125°C (-40°F to +257°F)
With diaphragm seal -70°C to +400°C (-94°F to +752°F)
Ambient temperature -40°C to +85°C (-40°F to +185°F)

Materials of Construction

Material selection for the PMP50 emphasizes corrosion resistance and process compatibility:

Process Membrane Materials:

316L stainless steel

Alloy C

Gold

Housing Materials:

Aluminum (standard)

316L stainless steel (for aggressive environments)

Fill Fluids:

Silicone oil (standard)

High-temperature oil

Inert oil (for oxygen service and other special applications)

Gasket Material: PTFE

 

Electrical Specifications

Parameter Non-Ex / Ex d / Ex e Ex i (Intrinsic Safety)
Supply voltage 10.5 to 35 V DC 10.5 to 30 V DC
Communication 4 to 20 mA HART 4 to 20 mA HART

 

The HART protocol enables simultaneous analog and digital communication, allowing remote configuration and diagnostics without interrupting the primary 4-20 mA signal loop.

Process Connections

The PMP50 accommodates various process connection standards:

Threaded Connections:

G1/2

NPT1/2

Flanged Connections:

DN25 to DN80

NPS 1″ to 3″

Order Code Breakdown: PMP50-AABAAJA6AA3HAA1SA0A1

The Endress+Hauser ordering code system provides a comprehensive specification of each device’s configuration. The complete order code PMP50-AABAAJA6AA3HAA1SA0A1 can be decoded as follows:

Position Segment Specification
1–4 PMP50 Product family: Cerabar PMP50 pressure transmitter
5–6 AA Approval / Certification (standard version, non-hazardous area)
7 B Output / Communication: 4-20 mA HART
8 A Process connection type: Threaded connection, standard
9 A Process connection size: G1/2
10 J Membrane material: 316L
11 A Fill fluid: Silicone oil
12 6 Measuring range / Sensor: Extended pressure range
13 A Housing type: Aluminum, standard
14 A Electrical connection: Cable gland M20x1.5
15–16 3H Display / Operation: Without local display, with push-buttons
17–18 AA Device version / Software: Standard HART version
19 1 Accuracy class: Platinum (±0.055%)
20 S Special version: Standard
21 A Calibration: Factory standard
22 0 Language: English
23 A Additional option 1: None
24 1 Additional option 2: None

This order code represents a PMP50 pressure transmitter configured for non-hazardous general industrial service, featuring 4-20 mA HART communication, G1/2 threaded connection, 316L process membrane, silicone oil fill fluid, aluminum housing, M20 cable gland entry, push-button operation, and Platinum-grade accuracy.

*Note: For precise decoding of each character position, refer to the official Endress+Hauser PMP50 ordering information documentation available via the W@M Device Viewer at www.endress.com/deviceviewer.*-

Certifications and Approvals

The Cerabar PMP50 series is developed and certified to meet rigorous international standards, making it suitable for deployment across global markets.

Explosion Protection Certifications

ATEX

FM (Factory Mutual)

IECEx

JPN Ex (Japan)

INMETRO (Brazil)

NEPSI (China)

Functional Safety

The PMP50 is designed in accordance with IEC 61508 and IEC 61511 standards, supporting SIL (Safety Integrity Level) functional safety certification up to SIL 2. This certification enables integration into safety instrumented systems (SIS) for critical process monitoring applications.-

Design and Material Approvals

EN10204-3.1 material traceability certification

NACE MR0103 (sour gas service)

NACE MR0175 (sour oil and gas production environments)

Core Product Features

Wizard-Guided Commissioning

The PMP50 incorporates a built-in software wizard that streamlines device setup, reducing commissioning time and minimizing the potential for configuration errors. This feature is particularly valuable for maintenance personnel who may encounter the device infrequently.

Flexible Write Protection

Hardware-based and software-based write protection options prevent unauthorized configuration changes, safeguarding measurement integrity in critical installations. The dual protection mechanism allows operators to balance security with operational flexibility.

Pre-Assembled Manifolds

Optional pre-assembled manifolds are pressure-tested and leakage-tested prior to shipment, accelerating field installation while ensuring proper sealing and operational readiness.

Field Serviceability Features

Zero/Span push-buttons for quick field recalibration

Test clamp for convenient loop testing without disconnecting wiring

RFID tag for electronic device identification and digital asset management

FLEX Modular Selection Concept

The PMP50 series aligns with Endress+Hauser’s FLEX modular selection framework, offering four pre-configured tiers:

Fundamental – Meet basic measurement needs

Lean – Handle core processes efficiently

Extended – Optimize processes with innovative technologies

Xpert – Master challenging applications

This modular approach enables precise specification matching of device capabilities to application requirements, preventing both over-specification and under-specification.

Application Scenarios

The Cerabar PMP50 pressure transmitter is engineered for standard industrial applications where reliability and accuracy are paramount. Typical deployments include:

Oil and Gas: Pipeline pressure monitoring, compressor station pressure measurement, wellhead pressure control

Chemical Processing: Reactor pressure monitoring, distillation column level measurement, storage tank pressure control

Power Generation: Boiler feedwater pressure monitoring, steam system pressure measurement, turbine inlet pressure control

Water and Wastewater Treatment: Distribution network pressure monitoring, pump suction and discharge pressure protection

Industrial Machinery: Hydraulic system pressure monitoring, test bench pressure measurement, OEM equipment integration

For high-temperature applications exceeding the standard -40°C to +125°C range, the PMP50 can be configured with a diaphragm seal, extending process temperature capability to 400°C (752°F) while maintaining measurement accuracy.-2

Complete Model Number Examples

To illustrate the ordering flexibility of the PMP50 series, the following complete model numbers represent common configurations:

PMP50-AAAAAJA6AA3HAA1SA0A1 – Basic configuration with standard accuracy

PMP50-BA1CAJA6AA3HAA1SA0A1 – ATEX certified version with threaded connection

PMP50-AABBAJA6AA3HAA1SA0A1 – NPT1/2 process connection with 316L membrane

PMP50-AABACJA6AA3HAA1SA0A1 – Alloy C process membrane for enhanced corrosion resistance

PMP50-AABAAJA6AA3HBA1SA0A1 – Stainless steel housing for harsh environments

PMP50-AABAAJA6AA3HCA1SA0A1 – High-temperature fill fluid for elevated process temperatures

PMP50-AABAAJA6AA3HAA2SA0A1 – Standard accuracy class (±0.065%)

PMP50-AABAAJA6AA3HAA1SB0A1 – Custom factory calibration

PMP50-AABAAJA6AA3HAA1SA1A1 – Optional display module

PMP50-AABAAJA6AA3HAA1SA0B1 – NEPSI certification for China market

Note: Specific configuration availability should be confirmed with Endress+Hauser or authorized distributors prior to ordering.

Documentation and Support

Endress+Hauser provides comprehensive documentation for the Cerabar PMP50 series, available through the official product portal at www.endress.com/deviceviewer. Key documents include:

Technical Information (TI01773P)

Operating Instructions (BA02332P)

Brief Operating Instructions (KA01679P)

Device Parameters / General Specifications (GP01222P)

These resources provide detailed installation guidance, configuration procedures, diagnostic information, and maintenance schedules.-1

Obtain relevant certificates and quotations for the product

Scroll to Top