pressure transmitter,temperature Transmitter,flow meter-ST-YK CLD

Emerson Rosemount 3101 Level Transmitter.

Model:3101LA1FRCNAFT

Manufacturer: ROSEMOUNT

Size: 40*80*25CM

Detail Specification:Level Transmitter.

Comment:Carton

Shipping Weight: 20Kg

Estimated Lead Time: 12 Weeks

Payment:T/T

HS CODE:9026809000

 

product details

Emerson Rosemount 3101 Level Transmitter.

Introduction

The Emerson Rosemount 3100 Series Ultrasonic Level Transmitter represents a reliable, non-contacting measurement solution for continuous liquid level monitoring across industrial applications. Manufactured under the Emerson Rosemount brand, this family of ultrasonic level transmitters delivers cost-effective performance for storage tanks, effluent pits, buffer tanks, reservoirs, and open channel flow applications-2.

The series comprises three primary models: the Rosemount 3101 Level Transmitter—the entry-level unit designed for simple level measurement with a 4–20 mA analog output—alongside the Rosemount 3102 and Rosemount 3105, which offer enhanced capabilities including HART communication, volume calculations, and open channel flow measurement-.

Product Status Notice: The Rosemount 3100 Series (3101, 3102, and 3105) has been discontinued as a standard catalog offering. This technical article is provided for reference purposes to support existing users and legacy system maintenance. For new installations, consult your local Emerson representative for current replacement solutions-8.

Ultrasonic Measurement Principle

The Rosemount 3100 Series operates on time-of-flight ultrasonic technology. The transmitter, mounted above the liquid surface, emits ultrasonic pulse signals directed toward the liquid. These pulses reflect off the liquid surface, and the transmitter “listens” for the returning echoes-24.

The microprocessor-controlled electronics calculate the distance to the liquid surface based on the time delay between transmission and reception-13. For the Rosemount 3101 specifically, the transmitter computes the liquid depth (level) and outputs the result as a 4–20 mA analog signal proportional to that level-16.

A critical component of the measurement accuracy is the integral temperature sensor, which continuously monitors air temperature around the transmitter. Since the speed of sound in air varies with temperature, the transmitter automatically compensates the calculated distance to eliminate temperature-induced errors-.

Detailed Technical Specifications

General Specifications

Parameter Specification
Product Family Rosemount 3100 Series Ultrasonic Level Transmitters
Model Numbers 3101, 3102, 3105
Product Status Discontinued (legacy/reference only)
Measurement Principle Ultrasonic, time-of-flight

Measurement Range

Model Maximum Range
Rosemount 3101 26 ft (8 m)
Rosemount 3102 36 ft (11 m)
Rosemount 3105 36 ft (11 m)

The usable measurement range begins at 1 ft (0.3 m) from the transmitter face for all models. The zone within 12 in. (0.3 m) of the transmitter face is the blanking distance—the sensor cannot reliably measure within this region-16.

Accuracy and Resolution

Parameter Rosemount 3101 Rosemount 3102 / 3105
Accuracy (<3.3 ft / 1 m) ±0.2 in. (5 mm) ±0.1 in. (2.5 mm)
Accuracy (>3.3 ft / 1 m) ±0.5% of measured distance ±0.25% of measured distance
Level Resolution Better than 0.04 in. (1 mm) Better than 0.04 in. (1 mm)

Reference conditions for accuracy specifications: 68 °F (20 °C), 1013 mbar atmospheric pressure, 50% relative humidity, calm and stable water surface-1.

Output Signals

Model Output Type
Rosemount 3101 4–20 mA analog only
Rosemount 3102 4–20 mA with HART digital communication
Rosemount 3105 4–20 mA with HART digital communication

The 3101 measures level exclusively. The 3102 and 3105 can calculate distance-to-surface, volume, or open channel flow, and output the result via the 4–20 mA signal and digital HART signal-24.

Measured Variables

3101: Level only

3102: Level, distance, volume, open channel flow

3105: Level, distance, volume, open channel flow

Power Supply and Electrical

Power Supply: Two-wire 24 Vdc loop-powered

Loop Voltage: 24 Vdc nominal (requires external power source)

Maximum DC Voltage: 30 V

Maximum Current: 21.75 mA-11

Environmental Ratings

Parameter Specification
Operating Temperature Range –4 °F to 158 °F (–20 °C to +70 °C)-11
Maximum Process Pressure 3 bar (43.51 psi)-
Housing Ingress Protection (Aluminum) NEMA 4X, IP66-1
Housing Ingress Protection (Polymer) IP66 / IP67

Materials of Construction

Component Material
Housing Options Polyurethane-covered die-cast aluminum or glass-filled nylon (engineered polymer)
Wetted Material PVDF (corrosion-resistant)
Conduit Entries (Metal Housing) ½-14 NPT
Conduit Entries (Polymer Housing) 2 x M20 with nylon cable glands-11
Mounting Thread 2-inch BSPT-11

Display and Configuration

Display: Integral 4/5-digit LCD (all models)

Configuration (3101): Integral push-buttons under housing cover

Configuration (3102 / 3105): Local membrane buttons, HART communication (Field Communicator, AMS Device Manager, or Rosemount 3490 Series Controller)

Remote Configuration (3102 / 3105): Via HART protocol

Temperature Compensation

3101: Integral temperature sensor only (automatic speed-of-sound correction)

3102 / 3105: Integral sensor standard; optional remote temperature sensor available for dynamic environments–24

Advanced Software Features (3102 and 3105 only)

Feature Description
Learn Routine (False Echo Registration) Transmitter can learn to ignore up to four false echoes caused by obstructions
Empty Tank Mapping Enables transmitter to map tank bottom for more accurate level calculations

Certifications and Approvals

3101: General purpose (not certified for hazardous areas)

3102: General purpose with integral signal relays

3105: Intrinsically safe certified (ATEX, CSA, IECEx, FM)

Dimensional Data

Height: Approximately 8.27 in. (210 mm) depending on housing configuration

Mounting: Above liquid surface using provided 2-inch thread; install as near vertical as possible for optimal echo reception

 

Complete Rosemount 3100 Series Model Number Reference

The Rosemount 3100 Series includes multiple configuration variants. Below are representative model codes for reference:

Model Number Configuration Description
3101L1 Ultrasonic level transmitter, 4–20 mA output, 1–26 ft range
3101L1P2 Basic level measurement, PVDF wetted material, glass-filled nylon housing
3101LP2FRCG5ST Ultrasonic level transmitter with integral display, buttons, temperature compensation, –30 °C to +70 °C operating range
3101LP3FSCNA 4–20 mA output, general-purpose configuration
3102 Ultrasonic level transmitter with 2 integral signal relays, HART communication
3105 Intrinsically safe ultrasonic level transmitter, HART communication, hazardous area certified

Note: The above model numbers are representative examples. Actual complete model numbers include additional position codes for range, housing material, conduit entry type, and certification requirements. Consult Emerson documentation for full model number construction guidelines.

Comparison: 3101 vs. 3102 vs. 3105

Feature Rosemount 3101 Rosemount 3102 Rosemount 3105
Primary Function Simple level measurement Level + local control Hazardous area measurement
Measurement Range 26 ft (8 m) 36 ft (11 m) 36 ft (11 m)
Output 4–20 mA analog 4–20 mA + HART 4–20 mA + HART
Integral Signal Relays No 2 relays No
Volume/Flow Calculations No Yes Yes
HART Communication No Yes Yes
Temperature Compensation Integral sensor Integral or remote sensor Integral or remote sensor
Hazardous Area Certification No No Yes (ATEX, CSA, IECEx, FM)
Remote Configuration No Via HART Via HART
Configuration Method Local push-buttons Local + HART Local + HART

Installation Guidelines for Rosemount 3100 Series

Proper installation is essential for accurate measurement and long-term reliability. Follow these procedures:

Mounting Requirements

Mount Above Liquid – The transmitter must be mounted above the liquid surface using the provided 2-inch thread-16.

Vertical Alignment – Install as near vertical as possible to ensure strong echo return and maximum echo size received-16.

Avoid Metal Fittings – Mount in a non-metallic fitting or flange to prevent signal interference-16.

Avoid Electrical Noise – Keep transmitter away from sources of electrical noise-16.

Blanking Zone – Ensure maximum liquid level does not enter the 12-in. (0.3-m) blanking zone at the transmitter face-16.

Avoid Inlet Streams – Do not mount directly over inlet streams where turbulence may affect echo quality-16.

Electrical Installation

The transmitter connects to any suitable 24 Vdc power source using two-core, shielded cable-16. For models with HART communication (3102 and 3105 only), a 250 Ω (minimum), 0.25 W load resistor must be installed in the loop-.

Configuration

3101 – Configure locally using integral push-buttons revealed after removing the housing cover-.

3102 / 3105 – Configure via local membrane buttons, Rosemount 3490 Series Control Unit, Field Communicator, or PC with AMS Suite: Intelligent Device Manager software-.

 

Typical Applications

The Rosemount 3100 Series was deployed across a wide range of industrial applications:

Storage Tank Level Monitoring – Continuous level measurement in chemical, water, and petrochemical storage tanks

Effluent Pits and Sump Monitoring – Reliable measurement in wastewater treatment applications

Buffer Tanks – Process buffer and surge tank level control

Reservoir Level Monitoring – Water and liquid reservoir level tracking

Open Channel Flow Measurement – Flow monitoring in open channels (3102 and 3105 only)

 

Legacy Support and Replacement Information

As the Rosemount 3100 Series is discontinued, customers currently operating legacy installations should note the following:

No Spare Parts Available – There are no spare parts for the Rosemount 3101, 3102, and 3105. If a problem persists, contact Rosemount Inc. for guidance-.

Mounting Flanges Available – Accessories such as mounting flanges for the 3101, 3102, and 3105 remain available from third-party suppliers-.

Replacement Recommendation – Consult your local Emerson representative for current-production alternatives offering similar or enhanced ultrasonic level measurement capabilities.

 

Compliance and Engineering Standards

The Rosemount 3100 Series was designed and manufactured in alignment with internationally recognized standards:

Ingress Protection – NEMA 4X, IP66 (aluminum housing); IP66/IP67 (polymer housing)

Hazardous Location Approvals (3105 only) – ATEX, CSA, IECEx, FM intrinsic safety

HART Communication Protocol – HART Revision D962-

 

 

 

Obtain relevant certificates and quotations for the product

Scroll to Top

Send Us a Message