pressure transmitter,temperature Transmitter,flow meter-ST-YK CLD

Honeywell DC1030 DIGITAL CONTROLLERS

Model:DC1030CR-101-000-E

Manufacturer: Honeywell

Size: 10*10*10cm

Detail Specification: DIGITAL CONTROLLERS

Comment:Carton

Shipping Weight: 4Kg

Estimated Lead Time: 12 Weeks

Payment:T/T

HS CODE:9026809000

product details

Honeywell DC1030 DIGITAL CONTROLLERS

Overview

The Honeywell DC1030 digital controller is a microprocessor-based instrument designed for precise temperature and process control across industrial applications. As part of the DC1000 family, the DC1030 model delivers a balanced combination of high functionality, field-proven reliability, and competitive pricing, making it a preferred choice for OEMs, panel builders, and system integrators-31. This technical resource provides comprehensive specifications for engineers and procurement professionals seeking detailed performance data.

Model Identification & Ordering

The Honeywell DC1030 belongs to the DC1000 series, which includes DC1010 (48×48mm), DC1020 (48×96mm), DC1030 (72×72mm), and DC1040 (96×96mm) panel sizes-31. Typical complete ordering codes include DC1030CR-101-000-E, DC1030CR-301-000-E, DC1030CR-20100B-E, DC1030CT-301000-E, and DC1030CL-331-000-E. These codes encode input type, output configuration, and optional features-2-24.

General Specifications

Parameter Value
Panel cutout dimensions 72×72 mm
Body dimensions (W×H×D) 72×72×94 mm
Mounting type Panel mount
Weight Approx. 300 g
Display Dual 4-digit 7-segment LED (PV red, SP green)
Display resolution 0.1°C for RTD PT100, 1°C for thermocouples
Bargraph 10-LED for control output (MV) indication

Input Specifications

The Honeywell DC1030 accepts a wide variety of sensor and signal inputs:

Input type Details
Thermocouples K, J, R, S, B, E, N, T, W, PL, U, L (12 types)
RTD PT100Ω, JPT100Ω, JPT50Ω (3 types)
Linear voltage –10–10mV, 0–10mV, 0–20mV, 0–50mV, 10–50mV, 0–1V, 0–5V, 0–10V, 1–5V, 2–10V
Linear current 0–20mA, 4–20mA
Input sampling time 250 ms
Input resolution 14 bits per channel
Input impedance Thermocouple / mV: >1MΩ; mA: 250Ω; V: ~500kΩ
Number of analog inputs 1–2 (configurable)
Display accuracy ±0.2% of full span
Cold junction compensation Automatic (built-in)

Output Specifications

Parameter Specifications
Relay output SPDT, 3A at 240VAC (resistive load)
Voltage pulse output 20VDC / 20mA (for SSR drive)
Linear analog output 0–20mA, 4–20mA, 0–5V, 0–10V, 1–5V, 2–10V
Motor control output Servo motor valve control (open-loop)
Solid-state relay drive Single-phase or three-phase SSR control
SCR firing control Single-phase or three-phase SCR, phase angle or zero-crossing
Number of analog outputs Up to 2
Number of digital outputs Up to 2 control outputs + 3 alarm outputs (optional)
Retransmission output PV, SP, or MV (4–20mA, 0–20mA, 0–5V, 0–10V, 1–5V, 2–10V)
Output cycle time 0–150 seconds (configurable; 0 for analog output)

Control Algorithms

The Honeywell DC1030 supports multiple control strategies:

PID control with auto-tuning capability (AT function) for automatic PID parameter optimization-

ON/OFF control (simple two-position control)

Heat/Cool control using two independent PID sets for dual-output applications

Motor position control without slidewire feedback

Single-phase SCR firing control with or without zero-crossing

Three-phase SCR firing control with or without zero-crossing-20

PID + Fuzzy logic for enhanced precision under varying process conditions-

Auto-Tuning Function

The auto-tuning feature calculates optimal PID values by performing a controlled oscillation of the process variable. ATVL (Auto-Tuning Value) parameter prevents overshoot during tuning by offsetting the tuning point below the setpoint. For example, with SP = 200°C and ATVL = 5, auto-tuning executes at 195°C-11.

Programming & Setpoint Functions

Parameter Value
Number of programs 2 independent programs
Segments per program Up to 8 segments
Maximum combined program length 16 segments (programs linked)
Segment features Repeatable loops, program linking, end-of-segment alarm output
Remote setpoint capability Supported via external input

Alarm Specifications

Parameter Specifications
Number of alarm outputs Up to 3 (optional)
Alarm modes 17 configurable types
Alarm timing Flash alarm, continuous alarm, delay timer alarm
Alarm assignment Can be assigned to PV, SP deviation, or MV

Communications

Protocol Details
Physical interface RS-232 or RS-485 (TTL level)
Protocol ASCII (Honeywell proprietary) or Modbus RTU
Baud rate Up to 38400 bps
Network capacity Up to 30 DC1000 controllers on a single RS-485 bus
Host functions Setpoint modification, PV monitoring, output reading, configuration changes

Environmental & Electrical

Parameter Value
Supply voltage 85–265 VAC, 50/60 Hz (universal) or 15–50 VDC (optional)
Power consumption Max. 4 VA
Operating temperature –20°C to +65°C (non-condensing)
Storage temperature –25°C to +70°C
Humidity 20–90% RH (non-condensing)
Front panel protection IP65 (dust-tight, protected against water jets)
Dielectric strength 2500 VAC for 1 minute between power and I/O terminals
Insulation resistance >10 MΩ at 500 VDC
Vibration resistance 10 m/s² (1G) at 10–55Hz, 10 min in X/Y/Z axes

Approvals & Compliance

CE marked (all models)

cUL certified (optional)

EEPROM non-volatile memory for data retention during power loss

Applications

The Honeywell DC1030 digital controller is suitable for:

Industrial ovens, furnaces, and dryers

Plastic processing machinery (extruders, injection molding)

Packaging equipment

Semiconductor packaging and testing

Painting and coating lines

Environmental chambers

HVAC systems

Accessories & Options

RS-232/RS-485 communication modules

Additional alarm output boards

Analog retransmission output

Remote setpoint input

 

Obtain relevant certificates and quotations for the product

Scroll to Top