Honeywell DC1030 DIGITAL CONTROLLERS
Model:DC1030CR-101-000-E
Manufacturer: Honeywell
Size: 10*10*10cm
Detail Specification: DIGITAL CONTROLLERS
Comment:Carton
Shipping Weight: 4Kg
Estimated Lead Time: 12 Weeks
Payment:T/T
HS CODE:9026809000
product details
Honeywell DC1030 DIGITAL CONTROLLERS
Overview
The Honeywell DC1030 digital controller is a microprocessor-based instrument designed for precise temperature and process control across industrial applications. As part of the DC1000 family, the DC1030 model delivers a balanced combination of high functionality, field-proven reliability, and competitive pricing, making it a preferred choice for OEMs, panel builders, and system integrators-31. This technical resource provides comprehensive specifications for engineers and procurement professionals seeking detailed performance data.
Model Identification & Ordering
The Honeywell DC1030 belongs to the DC1000 series, which includes DC1010 (48×48mm), DC1020 (48×96mm), DC1030 (72×72mm), and DC1040 (96×96mm) panel sizes-31. Typical complete ordering codes include DC1030CR-101-000-E, DC1030CR-301-000-E, DC1030CR-20100B-E, DC1030CT-301000-E, and DC1030CL-331-000-E. These codes encode input type, output configuration, and optional features-2-24.
General Specifications
| Parameter | Value |
| Panel cutout dimensions | 72×72 mm |
| Body dimensions (W×H×D) | 72×72×94 mm |
| Mounting type | Panel mount |
| Weight | Approx. 300 g |
| Display | Dual 4-digit 7-segment LED (PV red, SP green) |
| Display resolution | 0.1°C for RTD PT100, 1°C for thermocouples |
| Bargraph | 10-LED for control output (MV) indication |
Input Specifications
The Honeywell DC1030 accepts a wide variety of sensor and signal inputs:
| Input type | Details |
| Thermocouples | K, J, R, S, B, E, N, T, W, PL, U, L (12 types) |
| RTD | PT100Ω, JPT100Ω, JPT50Ω (3 types) |
| Linear voltage | –10–10mV, 0–10mV, 0–20mV, 0–50mV, 10–50mV, 0–1V, 0–5V, 0–10V, 1–5V, 2–10V |
| Linear current | 0–20mA, 4–20mA |
| Input sampling time | 250 ms |
| Input resolution | 14 bits per channel |
| Input impedance | Thermocouple / mV: >1MΩ; mA: 250Ω; V: ~500kΩ |
| Number of analog inputs | 1–2 (configurable) |
| Display accuracy | ±0.2% of full span |
| Cold junction compensation | Automatic (built-in) |
Output Specifications
| Parameter | Specifications |
| Relay output | SPDT, 3A at 240VAC (resistive load) |
| Voltage pulse output | 20VDC / 20mA (for SSR drive) |
| Linear analog output | 0–20mA, 4–20mA, 0–5V, 0–10V, 1–5V, 2–10V |
| Motor control output | Servo motor valve control (open-loop) |
| Solid-state relay drive | Single-phase or three-phase SSR control |
| SCR firing control | Single-phase or three-phase SCR, phase angle or zero-crossing |
| Number of analog outputs | Up to 2 |
| Number of digital outputs | Up to 2 control outputs + 3 alarm outputs (optional) |
| Retransmission output | PV, SP, or MV (4–20mA, 0–20mA, 0–5V, 0–10V, 1–5V, 2–10V) |
| Output cycle time | 0–150 seconds (configurable; 0 for analog output) |
Control Algorithms
The Honeywell DC1030 supports multiple control strategies:
PID control with auto-tuning capability (AT function) for automatic PID parameter optimization-
ON/OFF control (simple two-position control)
Heat/Cool control using two independent PID sets for dual-output applications
Motor position control without slidewire feedback
Single-phase SCR firing control with or without zero-crossing
Three-phase SCR firing control with or without zero-crossing-20
PID + Fuzzy logic for enhanced precision under varying process conditions-
Auto-Tuning Function
The auto-tuning feature calculates optimal PID values by performing a controlled oscillation of the process variable. ATVL (Auto-Tuning Value) parameter prevents overshoot during tuning by offsetting the tuning point below the setpoint. For example, with SP = 200°C and ATVL = 5, auto-tuning executes at 195°C-11.
Programming & Setpoint Functions
| Parameter | Value |
| Number of programs | 2 independent programs |
| Segments per program | Up to 8 segments |
| Maximum combined program length | 16 segments (programs linked) |
| Segment features | Repeatable loops, program linking, end-of-segment alarm output |
| Remote setpoint capability | Supported via external input |
Alarm Specifications
| Parameter | Specifications |
| Number of alarm outputs | Up to 3 (optional) |
| Alarm modes | 17 configurable types |
| Alarm timing | Flash alarm, continuous alarm, delay timer alarm |
| Alarm assignment | Can be assigned to PV, SP deviation, or MV |
Communications
| Protocol | Details |
| Physical interface | RS-232 or RS-485 (TTL level) |
| Protocol | ASCII (Honeywell proprietary) or Modbus RTU |
| Baud rate | Up to 38400 bps |
| Network capacity | Up to 30 DC1000 controllers on a single RS-485 bus |
| Host functions | Setpoint modification, PV monitoring, output reading, configuration changes |
Environmental & Electrical
| Parameter | Value |
| Supply voltage | 85–265 VAC, 50/60 Hz (universal) or 15–50 VDC (optional) |
| Power consumption | Max. 4 VA |
| Operating temperature | –20°C to +65°C (non-condensing) |
| Storage temperature | –25°C to +70°C |
| Humidity | 20–90% RH (non-condensing) |
| Front panel protection | IP65 (dust-tight, protected against water jets) |
| Dielectric strength | 2500 VAC for 1 minute between power and I/O terminals |
| Insulation resistance | >10 MΩ at 500 VDC |
| Vibration resistance | 10 m/s² (1G) at 10–55Hz, 10 min in X/Y/Z axes |
Approvals & Compliance
CE marked (all models)
cUL certified (optional)
EEPROM non-volatile memory for data retention during power loss
Applications
The Honeywell DC1030 digital controller is suitable for:
Industrial ovens, furnaces, and dryers
Plastic processing machinery (extruders, injection molding)
Packaging equipment
Semiconductor packaging and testing
Painting and coating lines
Environmental chambers
HVAC systems
Accessories & Options
RS-232/RS-485 communication modules
Additional alarm output boards
Analog retransmission output
Remote setpoint input