Rosemount 648 Wireless Temperature
Rosemount 648 Wireless Temperature
MODEL: 648DX1D1I1WA3WK1M5F5Q4G2
Manufacturer: Rosemount
Size:40*20*20cm
Detail Specification:Wireless Temperature Transmitter
Comment:Carton
Shipping Weight: 8 Kg
Estimated Lead Time: 6 – 8 Weeks
Payment:T/T
product details
Rosemount 648 Wireless Temperature
WirelessHART® Self-Organizing Network Technology: Data reliability >99%. Field temperature data can be integrated into the control system without laying signal cables, significantly reducing installation costs.
Dual-Compartment Housing Design: The terminal compartment and electronics compartment are isolated to prevent moisture and dust ingress from the field, improving long-term operational reliability.
Rosemount X-well™ Technology: When paired with a Rosemount 0085 clamp-on sensor, the transmitter’s built-in thermal conductivity algorithm directly measures pipe surface temperature — no thermowell or process penetration required — eliminating leak risk points and reducing design, installation, and maintenance costs.
Transmitter-Sensor Matching: Supports Callendar-Van Dusen constant input, writing sensor characteristic parameters into the transmitter to achieve higher measurement accuracy than standard matching.
SmartPower™ Module: Up to 10 years of maintenance-free operation. Field replacement can be done without removing the transmitter body, reducing downtime.
Model Code Explanation: 648DX1D1I1WA3WK1M5F5Q4G2
The following breaks down each code segment (based on the Emerson product data sheet):
| Code Segment | Meaning |
| 648 | Product series: Rosemount 648 Wireless Temperature Transmitter |
| D | Transmitter type: Wireless field mount |
| X | Output method: Wireless |
| 1 | Measurement configuration: Single-sensor input |
| D | Housing style: Dual-compartment field-mount housing |
| 1 | Conduit entry size: ½-14 NPT |
| I1 | Product certification: ATEX Intrinsic Safety |
| WA3 | Wireless update rate: User-configurable, 2.4 GHz DSSS, IEC 62591 (WirelessHART) |
| WK1 | Antenna and power module: External antenna, black power module adapter (intrinsically safe power module sold separately) |
| M5 | Display option: LCD display |
| F5 | Factory configuration: Factory configuration per order requirements (refer to Emerson data sheet for specific options) |
| Q4 | Calibration certificate: 3-point calibration certificate |
| G2 | Other options: Refer to the complete Emerson selection table for confirmation (commonly related to specific certifications or regional requirements) |
Selection Tip: Tail-end codes such as F5 and G2 may vary by product data sheet version and region. It is recommended to confirm with Emerson’s latest official selection tool before actual procurement.
Hot Models :
| 648DX1D1NAWA3WK1M5C1F5 |
| 648DX4D1I5WA3WK2M5F5 |
| 648DX3D3NAWA3WK1M5C1F5 |
| 648DX1D1IQWA3WK2M5F5 |
| 648DX1D1IMWA3WK1M5C1F5 |
| 648DX1D1I5WA3WK2M5F5 |
Typical Application Scenarios
Remote measurement points without mains power: Tank farms, pipe racks, and remote pipeline temperature monitoring, free from cable routing constraints.
High-risk or difficult-to-wire areas: Toxic media pipelines and rotating equipment surroundings. X-well technology eliminates penetration, reducing leak risks.
Rapid expansion of existing plants: New temperature measurement points can be added without shutdown or wiring. The SmartPower module supports 10 years of operation, enabling immediate commissioning.