pressure transmitter,temperature Transmitter,flow meter-ST-YK CLD

YOKOGAWA SDV521-S63

Model:SDV521-S63

Manufacturer: YOKOGAWA

Size: 20*20*30cm

Detail Specification: I/O module

Comment:Carton

Shipping Weight:0.39 Kg

Payment:T/T

HS CODE:8538900000

Unit price (EXW): 1217US dollars

Delivery time: 25 weeks

product details

YOKOGAWA SDV521-S63

The YOKOGAWA SDV521-S63 is a compact, high‑reliability digital output module engineered by Yokogawa Electric for mission‑critical industrial control and safety systems. As a key component of the ProSafe‑RS Safety Instrumented System (SIS) and CENTUM VP Distributed Control System (DCS), it delivers stable, high‑speed on/off control for field devices in harsh process environments. Built for module isolation, fast switching, and wide‑range operation, the SDV521-S63 ensures safe, precise control of solenoid valves, relays, motor starters, and interlocks—ideal for industries demanding functional safety and long‑term durability.

 

Model Code Explanation: SDV521-S63

To support clear selection and avoid misordering, the SDV521-S63 model code follows Yokogawa’s standard I/O module naming rules:

  • SDV521: Base model
    • SDV: Digital Output Module
    • 521: 4‑channel, module‑isolated type (24 VDC/2 A)
  • ‑S: Standard version (non‑explosion‑proof base unit)
  • 6: Signal cable adapter, non‑explosion‑proof
  • 3: Compliant with ISA G3; operating temperature ‑20°C to +70°C

Full meaning: YOKOGAWA SDV521-S63 = 4‑channel isolated digital output module, standard type, non‑exproof cable adapter, ISA G3, ‑20°C to +70°C.

Core Technical Specifications (Detailed Parameters)

General

  • Model: SDV521-S63
  • Manufacturer: YOKOGAWA (Yokogawa Electric, Japan)
  • Type: 4‑channel isolated digital output module
  • Output Configuration: Transistor sinking (current source)
  • Isolation: Module‑to‑bus isolation (no channel‑to‑channel isolation)
  • Rated Output Voltage: 24 VDC (external supply)
  • Output Voltage Range: 24 VDC +20% / –10%
  • Max Output Current: 2 A per channel
  • Min Load Current: 100 mA
  • Load Resistance: 12–240 Ω
  • Max Lamp Load: 1 A per channel
  • Output Voltage Drop: ≤ 1 V @ 2 A
  • Leakage Current (Off): ≤ 1.6 mA
  • Response Time: < 10 ms (on/off)
  • Power Consumption: ≤ 20 W (max)

Environmental

  • Operating Temperature: ‑20°C to +70°C (ISA G3)
  • Storage Temperature: ‑40°C to +85°C
  • Relative Humidity: 5%–95% RH (non‑condensing)
  • Pollution Degree: PD2
  • Altitude: Up to 2,000 m
  • Vibration Resistance: 5–150 Hz, 0.1 mm amplitude

Mechanical

  • Dimensions (W × H × D): 130 × 32.8 × 125.5 mm
  • Weight: 0.36 kg (0.79 lb)
  • Mounting: DIN rail (standard)
  • Housing: Flame‑retardant engineering plastic, IP20 (front)
  • Connection: Dedicated signal cable (AKB651 series)

System & Safety

  • Compatible Systems: ProSafe‑RS SIS, CENTUM VP DCS, N‑IO network
  • Safety Level: SIL 2 (per IEC 61508)
  • Certifications: CE, UL, CSA, ATEX (system‑dependent)
  • Diagnostics: Output short‑circuit, overload, open‑load, supply fault
  • Hot Swap: Supported (online replacement without shutdown)

Obtain relevant certificates and quotations for the product

Scroll to Top

Send Us a Message