pressure transmitter,temperature Transmitter,flow meter-ST-YK CLD

Yokogawa YTA50 Temperature Transmitter

Yokogawa YTA50 Temperature Transmitter

Model:YTA50-A/KS2

Manufacturer: YOKOGAWA

Size: 20*20*30cm

Detail Specification: temperature transmitter

Comment:Carton

Shipping Weight:0.5Kg

Estimated Lead Time: 12 Weeks

Payment:T/T

HS CODE:9026201090

Unit price (EXW): 460 US dollars

Delivery time: 12 – 16 weeks

product details

Yokogawa YTA50 Temperature Transmitter

The Yokogawa YTA50 is a head-mount temperature transmitter designed for precision and long-term stability. Accepting thermocouple, RTD, ohm, and DC millivolt inputs, this device delivers a 4 to 20 mA DC analog output proportional to measured temperature. Built for industrial environments and hazardous area installations, the YTA50 series remains a dependable choice worldwide.

This article covers complete technical specifications and provides a full model breakdown for YTA50-A/KS2 — a regular offering from ST-YUKE CO., LIMITED.

Overview

The Yokogawa YTA50 operates as a 2-wire analog temperature transmitter with microprocessor‑based sensing for high accuracy and signal integrity. It conforms to DIN Form B head mounting standards, making installation straightforward in most connection heads. Additionally, it supports both head mount and DIN rail mount configurations depending on application needs-24.

Thanks to its wide input selection and minimal straight‑pipe requirements, the Yokogawa YTA50 series fits diverse process environments requiring consistent, noise‑resistant temperature transmission.

Complete Technical Specifications

All data below applies to the YTA50‑A/KS2 and the broader YTA50 product family.

ParameterSpecification
ManufacturerYokogawa Electric Corporation
Product SeriesYTA50
Mounting TypeHead mount (DIN Form B compliant) / DIN rail mount (with optional kit)
Input TypesThermocouple (T/C), RTD (2‑, 3‑, 4‑wire), Ohm, DC millivolt
Output Signal4 to 20 mA DC, 2‑wire
Accuracy (typical)±0.1% of span or ±0.2°C (0.36°F), whichever greater
Cold Junction Compensation (T/C only)±1°C (±1.8°F)
Input Signal Source Resistance (T/C)10 MΩ (power on), 3 kΩ (power off)
Input Lead Wire Resistance (RTD)5 Ω per wire maximum
Response Time1 to 60 seconds (user‑programmable)
Power Supply Effect±0.005% of full scale per volt
Ambient Temperature Effect(±0.1% or ±0.1°C) per 10°C
Supply Voltage7 to 35 V DC (7 to 28 V DC for intrinsically safe)
Load Resistance739 Ω typical at 24 V DC supply
IsolationInput / output isolated to 1500 V AC
Enclosure MaterialPolycarbonate
Housing ColorRed
TerminalsM3 screws
Weight50 g (0.11 lb)
Ambient Temperature Limits–40 to 85°C (–40 to 185°F) (option code may affect limit)
Ambient Humidity Limits5 to 90% RH at 40°C (104°F)
EMC ConformityEN61326‑1 Class A, Table 2; EN61326‑2‑3
EU RoHS DirectiveApplicable (EN 50581)
Certifications (standard)CE; ATEX / IECEx / FM for intrinsically safe versions
Sensor BurnoutHigh or low output (user configurable)

*Data sources: GS 01C50C01-00EN, Yokogawa YTA50 Product Bulletin-1*

Input Range and Span Details

The YTA50 supports 16 different input types. For each sensor type, the minimum span is specified to ensure accurate signal conversion.

Sensor TypeStandard Input RangeMinimum SpanAccuracy
Type B (IEC584)400 to 1820°C200°C±0.1% of span or ±2.0°C
Type E–100 to 1000°C50°C±0.1% of span or ±1.0°C
Type J–100 to 1200°C50°C±0.1% of span or ±0.5°C
Type K–180 to 1372°C50°C±0.1% of span or ±0.5°C
Type N–180 to 1300°C50°C±0.1% of span or ±0.5°C
Type R–50 to 1760°C200°C±0.1% of span or ±2.0°C
Type S–50 to 1760°C200°C±0.1% of span or ±2.0°C
Type T–200 to 400°C50°C±0.1% of span or ±1.0°C
Pt100 RTD–200 to 850°C50°C±0.1% of span or ±0.2°C

*Data derived from Yokogawa GS 01C50C01-00EN specifications-1*

Model Code Breakdown: YTA50-A/KS2

The complete model YTA50-A/KS2 specifies a fully configured temperature transmitter. Below is a segment‑by‑segment explanation.

Model SegmentCodeDescription
Product SeriesYTA50Head‑mount temperature transmitter
Output Signal–A4 to 20 mA DC analog output
Suffix Code/KS2Intrinsically safe approval – CENELEC ATEX EEx ia IIC T1‑6 (Ambient temperature: T1‑4: –40 to 85°C / T5‑6: –40 to 65°C)

 

Obtain relevant certificates and quotations for the product

Scroll to Top

Send Us a Message